Generic hyperscale build-to-suit requirements. A tenant density or generator change resets the air, noise, utility and building processes at once, so the spec lock and the change-impact review are the schedule protection, not the spec acceptance itself.

Sources (2)

DocumentVersionEffectiveNotes
Lease / build-to-suit agreement — delivery milestones and liquidated damages (template)——
Tenant basis of design / technical specification (template)——Replace with the tenant's actual BOD revision and lease exhibit at onboarding.

Requirement classes (5)

Triggers are evaluated against project inputs; durations are typical working days.
CodeTitleGateCategoryAsset classesTriggerDaysVetoPredecessorsSource / clause
TEN-GEN
Generator, density and redundancy specification lock
Frozen generator fleet (count, kW, tier, emergency/non-emergency classification, run hours), rack density and redundancy (N+1, 2N) for the permit applications. Predecessor to the air pathway determination, noise study and fire marshal review; a change here re-opens all three.
Evidence: Spec-lock memo countersigned by tenant listing fleet, density and redundancy values used in permit filings.
EntitlementTenantData centerApplies when a tenant is named20TEN-SPEC
Tenant basis of design / technical specification (template)
—
TEN-SPEC
Design specification acceptance (basis of design)
Owner acceptance of the tenant's basis of design: power density, cooling method, redundancy topology, security and fiber. Every downstream study (air, noise, utility load) reads from this revision.
Evidence: Signed BOD acceptance with revision number; deviation log.
EntitlementTenantData centerApplies when a tenant is named40—
Tenant basis of design / technical specification (template)
—
TEN-LEASE
Lease execution and commencement conditions
Executed lease or build-to-suit agreement with the conditions to commencement (entitlements, power confirmation, financing). Lenders generally require the executed lease to close.
Evidence: Fully executed lease; schedule of commencement conditions with status.
PermitTenantData centerApplies when a tenant is named30TEN-SPEC, DOM-CAPACITY
Lease / build-to-suit agreement — delivery milestones and liquidated damages (template)
—
TEN-CHANGE
Change-order impact review across permits (change-impact protocol)
Agreed protocol that any tenant-initiated change to density, generators, cooling or layout is run through the register before acceptance, listing which air, noise, utility, fire and building items re-open and the schedule and LD consequence. Ties to the change-impact module.
Evidence: Signed change-impact protocol; impact memo on file for each change request.
ConstructionTenantData centerApplies when a tenant is named10TEN-GEN, TEN-MILESTONES
Lease / build-to-suit agreement — delivery milestones and liquidated damages (template)
—
TEN-MILESTONES
Delivery milestones and liquidated damages schedule
Lease exhibit of delivery milestones (shell, power on, ready for service by hall) with LDs, mapped to the approval critical path so each LD date has a named predecessor chain and float.
Evidence: Milestone exhibit with LD terms; schedule mapping of each milestone to register items.
ConstructionTenantData centerApplies when a tenant is named15TEN-LEASE
Lease / build-to-suit agreement — delivery milestones and liquidated damages (template)
—