Fire marshal plan review: lithium-ion UPS (NFPA 855), bulk diesel (NFPA 30), responder access

Not startedlibrary

Provenance

Source document
Virginia Uniform Statewide Building Code (2021 edition) and Statewide Fire Prevention Code (2021), as enforced by Loudoun Building and Development and the Fire Marshal's Office · 2021 VUSBC / 2021 SFPC · effective 2024-01-18
Clause
2021 SFPC / VUSBC; NFPA 855; NFPA 30; IFC Ch. 12
Trigger
Applies when generators with on-site diesel storage are proposed (generator count >= 1); battery MWh is reviewed in the same package
Description
Fire Marshal's Office review of energy storage / Li-ion UPS under NFPA 855 and IFC Ch. 12, bulk diesel storage under NFPA 30, clean-agent suppression and fire apparatus access. Interpretations vary by jurisdiction; secure them in writing early because re-review after a design change is common.
Evidence required
Fire marshal review letter; hazard mitigation analysis for ESS (NFPA 855); tank permit for diesel storage.